Metal-Oxide Surge Arresters in Power Grids

Featured image titled How to Choose Rating and Specifications for Metal-Oxide Surge Arresters in Power Grids, by RELCO Electricals
Surge Arrester Selection Guide: MCOV, Rated Voltage & Discharge Class | RELCO Electricals

How to Choose Rating and Specifications for Metal-Oxide Surge Arresters in Power Grids

A single lightning-induced surge on an 11 kV feeder can puncture transformer winding insulation in microseconds. The cost is rarely just the replacement unit: it is outage penalties, lost production at industrial consumers, emergency crews and weeks of lead time. Switching surges from capacitor banks, cable energisation and breaker restrikes do the same damage more quietly, stressing insulation until it fails on an ordinary day.

The metal-oxide surge arrester (MOSA, or MOV arrester) is the primary overvoltage protection equipment between those events and your insulation. But it protects only if correctly matched to the system. Too low a rating and it ages, overheats and fails during normal operation or a routine earth fault. Too high and it lets through residual voltages your transformer cannot tolerate.

This surge arrester selection guide covers the parameters that matter, a practical workflow for 11 kV and 33 kV networks, and the mistakes we see most in power grid surge protection specifications.

Core Electrical Parameters to Evaluate

Rated Voltage (Ur) vs. MCOV

  • MCOV (Uc): the highest power-frequency voltage the arrester withstands continuously without thermal instability. The MOV arrester MCOV rating must exceed the continuous phase-to-earth voltage, with margin for harmonics and regulation.
  • Rated voltage (Ur): the power-frequency voltage withstood for 10 seconds in the IEC 60099-4 operating duty test after energy injection. It anchors TOV capability and classification.

Ur is typically about 1.25 times Uc for gapless designs, but pairings vary by manufacturer. Read both from the datasheet.

Key metric: continuous phase-to-earth voltage is 6.93 kV on a healthy 11 kV system (Um = 12 kV) and 20.8 kV on a 33 kV system (Um = 36 kV), each equal to Um / √3. MCOV must exceed these, often by a wide margin because of earth faults.

Nominal Discharge Current (8/20 µs) and Energy Handling

Nominal discharge current (In) is the 8/20 µs peak used to classify the arrester and measure residual voltage. Distribution arresters are typically 5 kA or 10 kA; 10 kA is common at 33 kV and at important 11 kV substations. Also check:

  • Residual voltage: voltage across the arrester at nominal current; it sets the protection level your equipment sees.
  • Line discharge class (IEC 60099-4, Class 1 to 3): switching-surge energy capability. Long cable feeders and capacitor duty justify a higher class.
  • High-current (4/10 µs) and long-duration withstand: proof of survival under direct-stroke-type and long surges.

Duty Cycle and Temporary Overvoltage (TOV)

TOV is a power-frequency rise lasting from a fraction of a second to hours, caused by earth faults on non-effectively earthed systems, load rejection or ferroresonance. It heats the metal-oxide blocks. Each manufacturer publishes a TOV curve (permissible overvoltage as a multiple of Ur against time); a typical gapless arrester tolerates roughly 1.1 to 1.2 × Ur for 10 seconds after prior energy. Your worst credible TOV and clearing time must sit beneath that curve. This check most often separates a correct rating from an optimistic one.

Step-by-Step Selection Methodology

1. Nominal Un11 kV / 33 kV 2. Max system Um12 kV / 36 kV 4. Worst-case TOVUm/√3 × k, plus clearing time 3. Neutralearthing: k 5. Select MCOV UcTOV curve check, then Ur k about 1.4 (effective) up to 1.73 (isolated or resonant) Then confirm protection margin against equipment BIL
Figure 1. From nominal voltage to MCOV: the earthing system is the deciding input.
  1. Establish Um. 11 kV gives Um = 12 kV; 33 kV gives Um = 36 kV. Use measured maximum if the network runs persistently above nominal.
  2. Identify neutral earthing. In isolated, resistance or resonant systems, healthy phases can rise to line-to-line voltage (factor up to 1.73) until the fault clears, possibly hours.
  3. Calculate continuous and temporary voltages. Continuous = Um / √3; TOV = that value × earth fault factor. Record the clearing time.
  4. Choose Uc and Ur. Select the lowest catalog rating whose Uc exceeds the continuous voltage and whose TOV curve covers the worst case (table below).
  5. Select discharge current and class. Overhead 11 kV feeders in moderate-lightning areas typically use 5 or 10 kA Class 1. For 33 kV, substation entries, cable terminations and capacitor switching use 10 kA Class 2 or higher and verify kJ per kV of Ur against calculated switching energy.
  6. Verify protection margin. Target at least 1.2 (lightning) and 1.15 (switching) against BIL per IEC 60099-5. Indicatively, a 12 kV arrester with residual voltage near 35 to 40 kV protects a 75 kV BIL 11 kV transformer; a 30 kV arrester near 90 to 100 kV protects a 170 kV BIL 33 kV unit.
  7. Match housing and short-circuit rating. Choose porcelain or polymeric (silicone) housing, creepage for the pollution class, and a pressure-relief rating (typically 20 kA or more) above the local fault level.
  8. Define installation. Mounting position, lead lengths, earth resistance, ground-lead disconnector, surge counter or leakage monitor.
System (Um)EarthingTypical UrTypical Uc (MCOV)
11 kV (12 kV)Effectively earthed, fast clearing9 to 10 kV7.65 to 8.4 kV
11 kV (12 kV)Resistance earthed, clearing within seconds12 kV9.6 to 10.2 kV
11 kV (12 kV)Isolated or long-duration faults15 kV12 to 12.7 kV
33 kV (36 kV)Effective or resistance earthed, fast clearing30 kV24 to 24.4 kV
33 kV (36 kV)Isolated or long-duration faults36 kV29 kV

Worked Example: 11 kV Metal-Oxide Surge Arrester

A resistance-earthed 11 kV overhead feeder supplies a pole-mounted transformer (BIL 75 kV), with earth faults cleared in 3 seconds.

  • Um = 12 kV; continuous phase-to-earth voltage = 6.93 kV. With k = 1.73, TOV = 12 kV for up to 3 seconds.
  • A metal-oxide surge arrester 11 kV with Ur = 12 kV and Uc = 9.6 to 10.2 kV exceeds the continuous voltage, and its TOV curve at 3 seconds covers 12 kV.
  • At 10 kA, Class 1, residual voltage of about 35 to 40 kV gives a margin of roughly 1.9 against 75 kV BIL, leaving headroom for lead voltage drop.

11 kV vs. 33 kV Surge Arrester Parameters

Parameter11 kV network33 kV network
Maximum system voltage (Um)12 kV36 kV
Continuous phase-to-earth voltage6.93 kV20.8 kV
Typical Ur (resistance or isolated neutral)12 to 15 kV30 to 36 kV
Typical MCOV (Uc)9.6 to 12.7 kV24 to 29 kV
Nominal discharge current5 kA or 10 kA10 kA
Line discharge classClass 1 (Class 2 for cable or capacitor duty)Class 2 or higher
Typical equipment BIL75 kV170 kV
Indicative residual voltage at 10 kA35 to 40 kV90 to 100 kV
Min. creepage, heavy pollution (25 mm/kV of Um)about 300 mmabout 900 mm
Typical short-circuit rating10 to 20 kA20 kA or higher
Preferred placementTransformer terminals, line entry, cable sealing endsLine entry, transformer bushings, cable terminations

Values are indicative. Final selection must follow IEC 60099-4 and 60099-5 (or IS equivalents), the neutral earthing arrangement and the manufacturer’s guaranteed data.

Placement in the Substation

Surge voltage grows with distance from the arrester because travelling waves reflect and double at open terminals. Install the arrester as close as practicable to the equipment it protects.

Incoming line Isolator Breaker Power transformer Outgoing feeder Earth mat MOSAMOSA MOSA 1: line entry,line side of isolator MOSA 2: at transformer terminals,no switch in the path, shortest leads Earth resistance 5 ohm or less
Figure 2. Recommended MOSA positions relative to the isolator, breaker and transformer.
  • Connect the arrester directly to the transformer terminals, never behind a disconnect switch.
  • Add a line-entry arrester where an overhead line terminates at a substation or cable.
  • Calculate maximum separation distance with the IEC 60099-5 method; in compact 11 kV installations this usually means mounting within a few metres of the bushing.
  • Fit a ground-lead disconnector so a failed arrester separates from the system without causing a persistent fault.

Common Specification Mistakes to Avoid

1. Undersizing MCOV

Selecting on nominal voltage alone, especially on isolated or resistance-earthed systems, is the most costly mistake. An arrester with MCOV too close to the continuous phase voltage runs hot, accumulates leakage current and enters thermal runaway, often during an earth fault when healthy-phase voltage rises 73 per cent. The failure is frequently misattributed to lightning.

Fix: determine k from neutral earthing, check the TOV curve against actual clearing times, and keep MCOV above both continuous and temporary requirements.

2. Oversizing Without Checking Protection Margin

Every step up in Ur raises residual voltage and erodes margin against BIL. Pick the lowest rating that satisfies MCOV and TOV, then verify the 1.2 lightning margin.

3. Ignoring Pollution Levels

Coastal salt, cement dust and fertiliser deposits form conductive films that cause external flashover and uneven voltage distribution. Specify creepage by site class: a common planning figure is 25 mm per kV of Um for heavy pollution and about 31 mm per kV for very heavy pollution. Hydrophobic silicone housings are generally more resilient in contaminated sites.

4. Poor Earth and Lead Lengths

Lead inductance drops very roughly 1 to 1.6 kV per metre at typical lightning front times, and that adds directly to residual voltage at the equipment. Keep combined line and earth leads short and straight, avoid sharp bends, target 5 ohm or lower earth resistance, and bond arrester earth to the transformer tank and neutral earth.

5. Overlooking Energy Duty and Short-Circuit Rating

A light-duty arrester on a long cable feeder or capacitor-switched circuit risks energy failure, and a pressure-relief rating below the fault level risks violent failure. Calculate switching energy and confirm short-circuit withstand exceeds the local fault level.

Specification Checklist

  • System voltage, Um, frequency and neutral earthing method
  • Earth fault factor and maximum fault-clearing time
  • Required Ur and Uc, with TOV curve reference
  • Nominal discharge current, line discharge class and equipment BIL
  • Pollution class, minimum creepage and housing material
  • Short-circuit rating, mounting, terminals and accessories (ground-lead disconnector, insulating base, counter or monitor)
  • Standards and type-test reports (IEC 60099-4, or IS 15086 Part 4 for Indian projects)

Conclusion: Key Takeaways

  1. Start from Um and let the neutral earthing method set continuous and temporary voltage.
  2. Set MCOV above both, then confirm the TOV curve covers worst-case fault duration.
  3. Choose the lowest adequate Ur, then verify protection margin against BIL.
  4. Match discharge current and line discharge class to the real energy duty.
  5. Select creepage for the pollution class and short-circuit rating for the fault level.
  6. Install close to the equipment with the shortest possible leads and a low-resistance earth.

Talk to RELCO Electricals’ High-Voltage Protection Team

RELCO Electricals supplies metal-oxide surge arresters for 11 kV and 33 kV distribution networks, with rated voltages, discharge classes and housing options to match your grid and pollution conditions. Send us your system voltage, neutral earthing method and equipment BIL, and our engineers will recommend a rating, check your protection margins and provide a technical quotation.

Request the HV protection catalog

Ratings and values in this article are indicative engineering guidance. Validate final selection against applicable standards, your system studies and the manufacturer’s guaranteed technical data.

References and Further Reading

Standards

  • IEC 60099-4:2014: Surge arresters, Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
  • IEC 60099-5:2018: Surge arresters, Part 5: Selection and application recommendations.
  • IEEE C62.11-2020: Metal-oxide surge arresters for AC power circuits (above 1 kV).
  • IS 15086 (Part 4):2017 (BIS): Indian adoption of IEC 60099-4:2014. It replaces the older IS 3070 (Part 3):1993, which has been withdrawn.

Further reading

RELCO Electricals

About the Author

Meghna Baid

Meghna Baid is a marketing professional with 7 years of experience, specializing in the electrical industry. She excels in brand building, strategic messaging, and high-impact campaigns, blending creativity with data-driven precision. With a sharp understanding of B2B and technical markets, she crafts compelling narratives that drive results and build strong industry connections.